| C3-1 Main Input/Output Module (50700956) |
 |
 |
 |
The C3-1 Centurion Main Input/Output Module features a multitude of input and output options, as follows:
INPUTS: * All input options are individually software selectable. No jumpers required. * 32 Optically-Isolated DC Digital Inputs: NO or NC, (active high/active low), non-incendive. LED indicators. Approved for use with general purpose switches in hazardous areas. * 12 Analog Inputs: 4-20 mA or 0-5V, 10 bit hardware. * 8 Thermocouple Inputs: Type J or K, 12 bit hardware. Open thermocouple detection: drives channel reading high (max of scale). Cold junction compensation. * 1 Magnetic Pickup Input/AC Run Signal: 30 to 10kHz, 5 VAC rms min, 120 VAC rms max.
OUTPUTS: * 10 Digital Outputs: LED indicators. * Four (4) relay outputs, form C, dry contacts. * Four (4) FET outputs (source). * Two (2) IGBT outputs (sink). * 2 Analog Outputs (C3-1-A only): 4-20 mA, 16 bit hardware.
COMMUNICATION PORTS: * Port 1: Interface: RS232 or RS485. Protocol: Modbus RTU (slave). * Port 2 (SERIAL): Interface: RS232 or RS485. Protocol: Modbus RTU (slave), Proprietary (Configuration Transfer). * Port 2 (USB): Interface: USB 1.1 Compliant Port emulating RS232 communications via PC driver. Protocol: Modbus RTU (slave), Proprietary (Configuration Transfer). Connection: USB type B connector. Automatic selection of USB when a signal is detected on the USB type B connector. * Port 3: Interface: CAN. Protocol/Services: Proprietary communications for Expansion I/O Module support.
SPECIFICATIONS: * Power Input: 10-32 VDC * Operating Temperature: -40 to 85°C (-40 to 185°F). * Configuration: PC-based software MConfig Pro. * Dimensions: 13-1/8"W, 4-7/8"H, 2-1/2"D.
|
|
|
|
|
|
|